First, calculate the total volume of the space to be ventilated by multiplying its length, width, and height (Length × Width × Height). Then, by applying the standard air exchange rate coefficient for that specific type of space, the required airflow (Q in m³/h) is determined.
Next, the static pressure drop is determined using the appropriate performance curve, based on the duct dimensions and total length.
Static pressure drop is determined using the appropriate performance curve, based on the duct dimensions and total length.
Example 1:
Consider a workshop that requires an exhaust airflow rate of 8,495 m³/h. The installed duct is 35 meters long with a diameter of 20 inches. The static pressure drop for this system is calculated as follows:
Note:
If the duct route includes any elbows, tees, filters, or other obstructions, the equivalent length of each fitting must be added to the total duct length.
Example 2:
For a highly contaminated workshop environment—such as a foundry—with dimensions of 24 m (length) × 12 m (width) × 5.5 m (height), the standard air exchange rate for this type of application is 15 to 20 air changes per hour. Based on this, the required airflow capacity is estimated as follows:
To improve overall system efficiency, enhance performance, and allow for better airflow distribution, a total of 5 exhaust fan units are selected for this project.